DSX Access Systems, Inc. 10731 Rockwall Road Dallas, Texas 75238 / 888-419-8353 / 214-553-6140 / www.dsxinc.com
11/2012
Basic Architecture
The DSX-1048PKG includes a DSX-1040E Enclosure, a
DSX-1040CDM Communication Distribution Module and 4 –
1042 Intelligent Controllers. This provides 8 Reader Ports, 32
Inputs, and 16 Outputs. The DSX-1048 Package comes
complete with 32-1K ohm EOL Resistors, Lock & Key, Wire
Ties, Tamper Switch, an External Power Indicator and a DSX-
1040PDP Power Distribution Panel.
The DSX-1040CDM receives RS-485 communications from a
possible previous panel and regenerates the 4 wire-RS485 to
the next DSX-1048PKG. The DSX-1040CDM module also
distributes Slave Controller communication to the Slave panels
within the same enclosure. Each DSX-1042 is powered from
an individually fused 12 volt output from the DSX-1040CDM
Communications Distribution Module. The DSX-1040CDM
receives power from the DSX-1040PDP Power Distribution
Panel.
Used in conjunction with the DSX-1048PKG is a DSX-
1040PDP or Power Distribution Panel. The DSX-1040PDP
houses the panel and lock power supplies, backup batteries,
and fused power distribution module. The DSX-1040PDP is
comprised of a DSX-1040PE Enclosure, an SWS-150 15V
power supply for the Controllers, an SWS-150-[15] or [27] for
either 12Vor 24Vlocks, and a DSX-1040PDM. The DSX-
1040PDM performs several critical functions such as
supervising Power Supplies and Batteries, distributing power
through fused outputs, and providing battery charging circuits.
All Outputs are Class II, Power Limited.